Uses Of Educators
It’s
been reported several times that on the screw chillers that use Eductors
for the oil return, while operating at a low load condition it looks like the
educator doesn’t efficiently operate enough for returning the oil to oil
separator or the sump for maintaining the level of oil. It then causes the
chillers to completely shut down on the low oil, a result of retained oil in
refrigerant charge in evaporator.
For
this type of chillar that employs educator for returning oil, the main cause of
failure might not be the low load but a low lift. In a comfortable and cool
environment, the chiller load could be responsive to the temperature outdoor.
This is when it’s very hot outside but the heat flows into building rapidly and
the chiller load becomes high.
Cool temperature
When
the temperature outside is cool, little heat is required to be removed from
conditioned space and thus the load of the chillar is also low. This low load
of chillar is accompanied by low lift conditions as ambient temperature comes
down from the high value. This low lift is considered to be the main cause of a
loss in the effectiveness of educator. The educator gets driven by a difference
in pressure between the evaporator and the condenser. When the difference in
pressure falls, the capacity of inducing flow is also reduced. The capacity of
inducing flow of educator is proportional to square of difference in pressure.
Thus the difference reduction in pressure leads to induced reduction in flow to
approximately 25% of the design.